Dew-point calculator

Calculate the temperature at which the entered air state reaches saturation. The result supports condensation checks, low-temperature reviews, and humidity-control discussions.

INPUTS

Magnus approximation over liquid water: air and calculated dew point must stay within −45 to 60°C. Below 0°C this is a supercooled-water dew point, not frost point. Use calibrated RH referenced to water.

CALCULATED RESULTS

Dew point (over water)
—
Relative humidity
—
Surface condensation / margin
—
Water-vapour partial pressure
—
Saturation vapour pressure
—
Dry-bulb to dew-point spread
—

Dew point, formula and worked examples

Dew point is the temperature at which cooling air reaches saturation at unchanged water-vapour content. A surface at or below this temperature can collect condensation. A positive margin describes these inputs only; allow for sensor uncertainty and later cooling.

γ = ln(RH/100) + 17.62T/(243.12 + T); Td = 243.12γ/(17.62 − γ)

es(T) = 611.2 exp[17.62T/(243.12 + T)] Pa; RH = 100 es(Td)/es(T)

Temperatures are in °C. Coefficients and the −45 to 60°C water-equation range follow NPL: dew point and relative humidity. This is a screening approximation near atmospheric pressure, not a high-pressure gas or frost-point calculation. Dew points outside the range are rejected.

Magnus examples (over water)
Air °CRH %Dew point °CDew point °F
10806.7144.07
20509.2648.66
256016.6962.05
308026.1779.10
354019.3866.89

Common mistakes

Continue with your site task

METHOD AND BOUNDARY

How this result is calculated

The NPL Magnus water equation uses 611.2 Pa, a = 17.62 and b = 243.12°C. The inverse returns dew point; the ratio of saturation pressures returns RH. Surface margin equals surface temperature minus dew point.

What this tool does not decide

A dew point alone does not provide moisture load, equipment capacity, transient surface temperature, leakage, air-change rate, or a safe project margin.